LC1D12G7 - TeSys D IEC contactor, 12 A, 3 P, 7.5 HP at 480 VAC, non...
LC1D12G7 - CONTACTOR 600VAC 12AMP IEC +OPTIONS

LC1D12G7 - CONTACTOR 600VAC 12AMP IEC +OPTIONS

Square D

$82.65 $109.99
  • Free Shipping
  • Easy Returns
  • Secure Payment

Description

LC1D12G7 - TeSys D IEC contactor, 12 A, 3 P, 7.5 HP at 480 VAC, non reversing, 120 VAC 50/60 Hz coil. 


range
TeSys
product name
TeSys D
product or component type
Contactor
device short name
LC1D
contactor application
Motor control
Resistive load
utilisation category
AC-3
AC-4
AC-1
poles description
3P
power pole contact composition
3 NO
[Ue] rated operational voltage
Power circuit <= 690 V AC 25...400 Hz
Power circuit <= 300 V DC
[Ie] rated operational current
25 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
12 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
motor power kW
3 kW at 220...230 V AC 50/60 Hz (AC-3)
5.5 kW at 380...400 V AC 50/60 Hz (AC-3)
5.5 kW at 415...440 V AC 50/60 Hz (AC-3)
7.5 kW at 500 V AC 50/60 Hz (AC-3)
7.5 kW at 660...690 V AC 50/60 Hz (AC-3)
3.7 kW at 400 V AC 50/60 Hz (AC-4)
motor power HP (UL / CSA)
0.5 hp at 115 V AC 50/60 Hz for 1 phase motors
2 hp at 230/240 V AC 50/60 Hz for 1 phase motors
3 hp at 200/208 V AC 50/60 Hz for 3 phases motors
3 hp at 230/240 V AC 50/60 Hz for 3 phases motors
7.5 hp at 460/480 V AC 50/60 Hz for 3 phases motors
10 hp at 575/600 V AC 50/60 Hz for 3 phases motors
control circuit type
AC at 50/60 Hz
[Uc] control circuit voltage
120 V AC 50/60 Hz
auxiliary contact composition
1 NO + 1 NC
[Uimp] rated impulse withstand voltage
6 kV IEC 60947
overvoltage category
III
[Ith] conventional free air thermal current
25 A (at 60 °C) for power circuit
10 A 140 °F (60 °C) signalling circuit
Irms rated making capacity
250 A at 440 V for power circuit conforming to IEC 60947
140 A AC signalling circuit IEC 60947-5-1
250 A DC signalling circuit IEC 60947-5-1
rated breaking capacity
250 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
105 A 40 °C - 10 s for power circuit
210 A 40 °C - 1 s for power circuit
30 A 40 °C - 10 min for power circuit
61 A 40 °C - 1 min for power circuit
100 A - 1 s signalling circuit
120 A - 500 ms signalling circuit
140 A - 100 ms signalling circuit
associated fuse rating
10 A gG signalling circuit IEC 60947-5-1
40 A gG at <= 690 V coordination type 1 for power circuit
25 A gG at <= 690 V coordination type 2 for power circuit
average impedance
2.5 mOhm - Ith 25 A 50 Hz for power circuit
[Ui] rated insulation voltage
Power circuit 690 V IEC 60947-4-1
Power circuit 600 V CSA
Power circuit 600 V UL
Signalling circuit 690 V IEC 60947-1
Signalling circuit 600 V CSA
Signalling circuit 600 V UL
electrical durability
2 Mcycles 12 A AC-3 at Ue <= 440 V
0.8 Mcycles 25 A AC-1 at Ue <= 440 V
power dissipation per pole
0.36 W AC-3
1.56 W AC-1
Front cover
With
mounting support
Rail
Plate
standards
CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
product certifications
DNV
GOST
GL
CSA
BV
LROS (Lloyds register of shipping)
UL
RINA
CCC
connections - terminals
Power circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Power circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Power circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Power circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Power circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)solid without cable end
Power circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)solid without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²)flexible with cable end
Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
tightening torque
Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2
operating time
12...22 ms closing
4...19 ms opening
safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
mechanical durability
15 Mcycles
maximum operating rate
3600 cyc/h 60 °C
Complementary
coil technology
Without built-in suppressor module
control circuit voltage limits
0.3...0.6 Uc -40…158 °F (-40…70 °C) drop-out AC 50/60 Hz
0.8...1.1 Uc -40…140 °F (-40…60 °C) operational AC 50 Hz
0.85...1.1 Uc -40…140 °F (-40…60 °C) operational AC 60 Hz
1...1.1 Uc 140…158 °F (60…70 °C) operational AC 50/60 Hz
inrush power in VA
70 VA 60 Hz cos phi 0.75 (at 20 °C)
70 VA 50 Hz cos phi 0.75 (at 20 °C)
hold-in power consumption in VA
7.5 VA 60 Hz cos phi 0.3 (at 20 °C)
7 VA 50 Hz cos phi 0.3 (at 20 °C)
heat dissipation
2…3 W at 50/60 Hz
auxiliary contacts type
Mechanically linked 1 NO + 1 NC IEC 60947-5-1
Mirror contact 1 NC IEC 60947-4-1
signalling circuit frequency
25...400 Hz
minimum switching current
5 mA signalling circuit
minimum switching voltage
17 V signalling circuit
non-overlap time
1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
insulation resistance
> 10 MOhm signalling circuit
contact compatibility
M2
compatibility code
LC1D
Environment
IP degree of protection
IP20 front face IEC 60529
protective treatment
TH IEC 60068-2-30
pollution degree
3
ambient air temperature for operation
-40…140 °F (-40…60 °C)
140…158 °F (60…70 °C) with derating
ambient air temperature for storage
-76…176 °F (-60…80 °C)
operating altitude
0...3000 m
fire resistance
850 °C conforming to IEC 60695-2-1
flame retardance
V1 UL 94
mechanical robustness
Vibrations contactor open: 2 Gn, 5...300 Hz
Vibrations contactor closed: 4 Gn, 5...300 Hz
Shocks contactor open: 10 Gn for 11 ms
Shocks contactor closed: 15 Gn for 11 ms
height
3.03 in (77 mm)
width
1.77 in (45 mm)
depth
3.39 in (86 mm)
net weight
0.72 lb(US) (0.325 kg)
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Weight
12.91 oz (366 g)
Package 1 Height
2.20 in (5.6 cm)
Package 1 width
3.70 in (9.4 cm)
Package 1 Length
4.65 in (11.8 cm)
Offer Sustainability
Sustainable offer status
Green Premium product
REACh Regulation
REACh free of SVHC
Yes
EU RoHS Directive
Toxic heavy metal free
Yes
Mercury free
Yes
RoHS exemption information
China RoHS Regulation
China RoHS declaration
 Pro-active China RoHS declaration (out of China RoHS legal scope)
Environmental Disclosure
Circularity Profile
WEEE
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
PVC free
Yes
Contractual warranty
Warranty
18 months



Authorized Square D Distributor **Beware of buying counterfeit electrical products** Looking for a product you don't see? Call our knowledgeable sales staff 800-347-0794

VOLUME PRICING

Call us to find out about volume pricing

BEWARE

Beware of counterfeit electrical products. We are authorized distributors for all the brands on this site.