LC1D12B7 - TeSys D IEC contactor, 12 A, 3 P, 7.5 HP at 480 VAC,...
Description
LC1D12B7 - TeSys D IEC contactor, 12 A, 3 P, 7.5 HP at 480 VAC, non reversing, 24 VAC 50/60 Hz coil
Authorized Square D Distributor **Beware of buying counterfeit electrical products** Looking for a product you don't see? Call our knowledgeable sales staff 800-347-0794
range |
TeSys
|
|
---|---|---|
product name |
TeSys D
|
|
product or component type |
Contactor
|
|
device short name |
LC1D
|
|
contactor application |
Resistive load
Motor control |
|
utilisation category |
AC-3
AC-1 AC-4 |
|
poles description |
3P
|
|
power pole contact composition |
3 NO
|
|
[Ue] rated operational voltage |
Power circuit <= 690 V AC 25...400 Hz
Power circuit <= 300 V DC |
|
[Ie] rated operational current |
25 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit
12 A 140 °F (60 °C)) <= 440 V AC AC-3 power circuit |
|
motor power kW |
3 kW 220...230 V AC 50/60 Hz AC-3)
5.5 kW 380...400 V AC 50/60 Hz AC-3) 5.5 kW 415...440 V AC 50/60 Hz AC-3) 7.5 kW 500 V AC 50/60 Hz AC-3) 7.5 kW 660...690 V AC 50/60 Hz AC-3) 3.7 kW 400 V AC 50/60 Hz AC-4) |
|
motor power HP (UL / CSA) |
0.5 hp 115 V AC 50/60 Hz 1 phase
2 hp 230/240 V AC 50/60 Hz 1 phase 3 hp 200/208 V AC 50/60 Hz 3 phase 3 hp 230/240 V AC 50/60 Hz 3 phase 7.5 hp 460/480 V AC 50/60 Hz 3 phase 10 hp 575/600 V AC 50/60 Hz 3 phase |
|
control circuit type |
AC 50/60 Hz
|
|
[Uc] control circuit voltage |
24 V AC 50/60 Hz
|
|
auxiliary contact composition |
1 NO + 1 NC
|
|
[Uimp] rated impulse withstand voltage |
6 kV IEC 60947
|
|
overvoltage category |
III
|
|
[Ith] conventional free air thermal current |
25 A 140 °F (60 °C) power circuit
10 A 140 °F (60 °C) signalling circuit |
|
Irms rated making capacity |
250 A 440 V power circuit IEC 60947
140 A AC signalling circuit IEC 60947-5-1 250 A DC signalling circuit IEC 60947-5-1 |
|
rated breaking capacity |
250 A 440 V power circuit IEC 60947
|
|
[Icw] rated short-time withstand current |
105 A 104 °F (40 °C) - 10 s power circuit
210 A 104 °F (40 °C) - 1 s power circuit 30 A 104 °F (40 °C) - 10 min power circuit 61 A 104 °F (40 °C) - 1 min power circuit 100 A - 1 s signalling circuit 120 A - 500 ms signalling circuit 140 A - 100 ms signalling circuit |
|
associated fuse rating |
10 A gG signalling circuit IEC 60947-5-1
40 A gG <= 690 V type 1 power circuit 25 A gG <= 690 V type 2 power circuit |
|
average impedance |
2.5 mOhm - Ith 25 A 50 Hz power circuit
|
|
[Ui] rated insulation voltage |
Power circuit 690 V IEC 60947-4-1
Power circuit 600 V CSA Power circuit 600 V UL Signalling circuit 690 V IEC 60947-1 Signalling circuit 600 V CSA Signalling circuit 600 V UL |
|
electrical durability |
2 Mcycles 12 A AC-3 <= 440 V
0.8 Mcycles 25 A AC-1 <= 440 V |
|
power dissipation per pole |
0.36 W AC-3
1.56 W AC-1 |
|
Front cover |
With
|
|
mounting support |
Rail
Plate |
|
standards |
CSA C22.2 No 14
EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 |
|
product certifications |
CCC
CSA GL GOST BV DNV RINA LROS (Lloyds register of shipping) UL |
|
connections - terminals |
Power circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible without cable end
Power circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)flexible without cable end Power circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)flexible with cable end Power circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²)flexible with cable end Power circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²)solid without cable end Power circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²)solid without cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end |
|
tightening torque |
Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2 Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2 |
|
operating time |
12...22 ms closing
4...19 ms opening |
|
safety reliability level |
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
|
mechanical durability |
15 Mcycles
|
|
maximum operating rate |
3600 cyc/h 140 °F (60 °C)
|
coil technology |
Without built-in suppressor module
|
|
---|---|---|
control circuit voltage limits |
0.3...0.6 Uc -40…158 °F (-40…70 °C) drop-out AC 50/60 Hz
0.8...1.1 Uc -40…140 °F (-40…60 °C) operational AC 50 Hz 0.85...1.1 Uc -40…140 °F (-40…60 °C) operational AC 60 Hz 1...1.1 Uc 140…158 °F (60…70 °C) operational AC 50/60 Hz |
|
inrush power in VA |
70 VA 60 Hz 0.75 68 °F (20 °C))
70 VA 50 Hz 0.75 68 °F (20 °C)) |
|
hold-in power consumption in VA |
7.5 VA 60 Hz 0.3 68 °F (20 °C))
7 VA 50 Hz 0.3 68 °F (20 °C)) |
|
heat dissipation |
2…3 W 50/60 Hz
|
|
auxiliary contacts type |
Mechanically linked 1 NO + 1 NC IEC 60947-5-1
Mirror contact 1 NC IEC 60947-4-1 |
|
signalling circuit frequency |
25...400 Hz
|
|
minimum switching current |
5 mA signalling circuit
|
|
minimum switching voltage |
17 V signalling circuit
|
|
non-overlap time |
1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact |
|
insulation resistance |
> 10 MOhm signalling circuit
|
|
contact compatibility |
M2
|
|
compatibility code |
LC1D
|
|
motor power range |
4…6 kW 380…440 V 3 phase
4…6 kW 480…500 V 3 phase 2.2…3 kW at 200…240 V 3 phases |
|
motor starter type |
Direct on-line contactor
|
|
contactor coil voltage |
24 V AC standard
|
IP degree of protection |
IP20 front face IEC 60529
|
|
---|---|---|
protective treatment |
TH IEC 60068-2-30
|
|
pollution degree |
3
|
|
ambient air temperature for operation |
-40…140 °F (-40…60 °C)
140…158 °F (60…70 °C) with derating |
|
ambient air temperature for storage |
-76…176 °F (-60…80 °C)
|
|
operating altitude |
0...9842.52 ft (0...3000 m)
|
|
fire resistance |
1562 °F (850 °C) IEC 60695-2-1
|
|
flame retardance |
V1 UL 94
|
|
mechanical robustness |
Vibrations contactor open2 Gn, 5...300 Hz
Vibrations contactor closed4 Gn, 5...300 Hz Shocks contactor open10 Gn for 11 ms Shocks contactor closed15 Gn for 11 ms |
|
height |
3.03 in (77 mm)
|
|
width |
1.77 in (45 mm)
|
|
depth |
3.39 in (86 mm)
|
|
Net Weight |
0.72 lb(US) (0.325 kg)
|
Category |
22354 - CTR,TESYS D,OPEN,9-38A AC
|
|
---|---|---|
Discount Schedule |
I12
|
|
GTIN |
00785901207016
|
|
Nbr. of units in pkg. |
1
|
|
Package weight(Lbs) |
0.79 lb(US) (0.36 kg)
|
|
Returnability |
Yes
|
|
Country of origin |
ID
|
Unit Type of Package 1 |
PCE
|
|
---|---|---|
Package 1 Height |
1.97 in (5 cm)
|
|
Package 1 width |
3.62 in (9.2 cm)
|
|
Package 1 Length |
4.41 in (11.2 cm)
|
|
Unit Type of Package 2 |
S02
|
|
Number of Units in Package 2 |
20
|
|
Package 2 Weight |
16.88 lb(US) (7.655 kg)
|
|
Package 2 Height |
5.91 in (15 cm)
|
|
Package 2 width |
11.81 in (30 cm)
|
|
Package 2 Length |
15.75 in (40 cm)
|
|
Unit Type of Package 3 |
P06
|
|
Number of Units in Package 3 |
320
|
|
Package 3 Weight |
288.06 lb(US) (130.66 kg)
|
|
Package 3 Height |
31.50 in (80 cm)
|
|
Package 3 width |
31.50 in (80 cm)
|
|
Package 3 Length |
23.62 in (60 cm)
|
Sustainable offer status |
Green Premium product
|
|
---|---|---|
California proposition 65 |
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
|
|
REACh Regulation | ||
REACh free of SVHC |
Yes
|
|
EU RoHS Directive |
Compliant
EU RoHS Declaration |
|
Toxic heavy metal free |
Yes
|
|
Mercury free |
Yes
|
|
RoHS exemption information | ||
China RoHS Regulation |
China RoHS declaration
Pro-active China RoHS declaration (out of China RoHS legal scope) |
|
Environmental Disclosure | ||
Circularity Profile | ||
WEEE |
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
|
|
PVC free |
Yes
|
Warranty |
18 months
|
---|